GLORIA 3PHASES LAND ALTERNATOR-GR270K | |||||||
C0NTROL SYSTEM | SEPARATELY EXCITED BY P.M.G. | ||||||
AVR | MX341 | ||||||
VOLTAGE REGULATION | ±1.0% | ||||||
SUSTAINED SHORT CIRCUIT | REFER TO SHORT CIRCUIT DECREMENT CURVES | ||||||
CONTROL SYSTEM | SELF EXCITED | ||||||
A.V.R. | SX460 | ||||||
VOLTAGE REGULATION | ±1.0 % | ||||||
SUSTAINED SHORT CIRCUIT | SERIES 4 CONTROL DOES NOT SUSTAIN A SHORT CIRCUIT CURRENT | ||||||
INSULATION SYSTEM | H | ||||||
PROTECEION | IP21-23 | ||||||
RATED POWER FACTOR | 0.8 | ||||||
STATOR WINDONG | DOUBLE LAYER CONCENTRIC | ||||||
WINDING PITCH | TWO THIRDS | ||||||
WINDING LEADS | 12 | ||||||
STATOR WDG.RESISTANCE | 0.01317Ω(27°C) | ||||||
ROTOR WDG.RESISTANCE | 2.2960Ω(27°C) | ||||||
EXCITER STATOR RESISTANCE | 20.16Ω(27°C) | ||||||
EXCITER ROTOR RESISTANCE | 0.09561Ω(27°C) | ||||||
R.F.I.SUPPRESSION | BS EN6000-6-2 & BS EN61000-6-4,VDE 1875G,VDE0875N.refer to factory for others | ||||||
WAVEFORM DISTORTION | <1.5% | ||||||
MAXIMUM OVERSPEED | 2250 Rev/Min | ||||||
BEARING DRIVE END | 63152RZ | ||||||
BEARING NON-DRIVE END | 63102RZ | ||||||
1 BEARING | 2 BEARING | ||||||
WEIGHT COMP.GENERATOR | 720KG | 730KG | |||||
WEIGHT WOUND STATOR | 290KG | 290KG | |||||
WEIGHT WOUND ROTOR | 252KG | 246KG | |||||
WR² INERTIA | 2.3934kgm² | ||||||
SHIPPING WEIGHTS in acrate | 760KG | 780KG | |||||
PACKING CRATE SIZE | 125*76*102(CM) | 125*76*102(CM) | |||||
50 Hz | 60 Hz | ||||||
TELEPHONE INTERFERENCE | THF<2% | TIF<50 | |||||
COOLING AIR | 0.58 m³/sec 1230 cfm | 0.69 m³/sec 1463 cfm | |||||
VOLTAGE SERIES STAR | 380/220 | 400/231 | 415/240 | 416/240 | 440/254 | 460/266 | 480/277 |
VOLTAGE PARALLEL STAR | 190/110 | 200/115 | 208/120 | 208/120 | 220/127 | 230/133 | 240/138 |
VOLTAGE SERIFS DELTA | 190/110 | 230/115 | 240/120 | 240/120 | 254/127 | 266/133 | 277/138 |
KVA BASE RATING FOR REACTANCE VALUES |
250 | 250 | 250 | 291 | 299 | 299 | 312.5 |
XdDIR.SNCHRONOUS | 2.825 | 2.55 | 2.369 | 3.161 | 2.903 | 2.776 | 2.55 |
X'd DIR.AXIS TRANSIENT | 0.132 | 0.119 | 0.111 | 0.148 | 0.136 | 0.13 | 0.119 |
X"d DIR.AXIS SUBTRANSIENT | 0.086 | 0.078 | 0.072 | 0.097 | 0.089 | 0.085 | 0.078 |
Xq QUAD.AXIS REACTANCE | 1.263 | 1.14 | 1.059 | 1.413 | 1.298 | 1.241 | 1.14 |
X"q QUAD.AXIS SUBTRANSIENT | 0.152 | 0.137 | 0.127 | 0.17 | 0.156 | 0.149 | 0.137 |
XL LEAKAGE REACTANCE | 0.666 | 0.06 | 0.056 | 0.074 | 0.068 | 0.065 | 0.06 |
X2 NEGATIVE SEQUENCE | 0.12 | 0.108 | 0.1 | 0.134 | 0.123 | 0.118 | 0.108 |
X0 ZERO SEQUENCE | 0.022 | 0.02 | 0.019 | 0.025 | 0.023 | 0.022 | 0.02 |
REACTANCES ARE SATURATED VALUES ARE PER UNIT RATING AND VOLACE INDICATED | |||||||
T'd TRANSIENT TIME CONST. | 0.049s | ||||||
T"d SUB-TRANSTIME CONST | 0.02s | ||||||
T'do O.C.FIELDTIME CONST. | 1.27s | ||||||
Ta ARMATURE CONST. | 0.018s | ||||||
SHORT CIRCUIT RATIO | 1/xd |
1.Question : Your product power range? | |
1.Answer : Power station diesel engine 180kw-1100kw standby power (high pressure common rail), ship engine diesel engine 83HP-1000HP main use | |
2.Question :The markets you now export to | |
2.Answer : Russia, Turkey, Peru, South Korea, Taiwan, Indonesia, Vietnam, Romania, Poland, Nigeria, Maldives | |
3.Question : Whether Waring products are available for purchase | |
3.Answer : For Russian customers who understand our Waring products, we can sell domestic low-grade Waring, and for those who have no specific needs, we do not mainly promote low-end Waring models | |
4.Question : How long is the product shelf life? | |
4.Answer : In principle, it is 1000 hours or 1 year, and it can be analyzed for special circumstances and models, such as extending to 1 and a half years, or starting from the date of the order between the customer and the terminal | |
5.Question : What are the application areas of diesel engines | |
5.Answer : Land power generation, Marine power, Marine power generation, drilling, mining, smelting, fire protection, agricultural irrigation, etc | |
6.Question :How long does it take to overhaul | |
6.Answer : Series 135, 10,000 hours, or 12,000 hours |